Ques 71. Which of the following factor should be identical for two alternators running in parallel?
Phase sequence
Voltage
Frequency
All of the above
Answer 4. All of the above
Explanation:
Condition for parallel operation of an alternator
There are five conditions that must be met before when two alternators running in parallel.
Equal line voltage
Same frequency
Same phase sequence
Same phase angle
Same waveform
Same Phase sequence
During the installation of a generator, carefully ensure the generator terminals and all control wiring is correct so that the order of phases (phase sequence) matches the system.
Connecting a generator with the wrong phase sequence will result in a short circuit as the system.
If we will connect any of the alternators with the opposite phase sequence then the voltages of both the alternator will become opposite to each other.
Same Frequency
The frequency of two alternators should be the same otherwise it will cause high acceleration and de-acceleration in the prime mover hence this will result in large power transient in the power system.
Equal line voltage
The line voltage of an alternator should be the same as the voltage of a bus bar.
If the voltage on the alternator will be more than the bus bar then generator will deliver unnecessary high reactive power to the grid.
If the voltage of bus bar is more than the alternator then generator will absorb high reactive power from the grid or busbar.
Ques 72. The main reason for the voltage drop in an alternator is
Armature resistance
Synchronous Reactance
Armature Reactance
All of the above
Answer 4. All of the above
Explanation:
Voltage Drop due to Armature Resistance
The voltage drop caused by armature resistance per phase is IRa Where I is phase current in ampere and Ra is armature resistance in ohm.
Additional energy loss such as Hysteresis loss, Eddy current Loss, and loss due to unequal distribution of currents are part of armature resistance losses.
Armature Leakage Reactance
When the load current flows through the armature winding it builds up the local flux which cuts the winding and counters EMF is generated. This effect produces armature reactance that is equal to 2πfl.
This armature reactance is called leakage reactance XL. and this leakage flux is proportional to the armature current.
Armature Reaction
When the load current flows in the stator conductor it produces the magnetic field which has a cross-magnetization, de-magnetization, and magnetizing effect upon the main flux due to the field windings.
Such an effect of armature current upon the main flux is known as armature reaction.
The armature reaction depends upon the power factor of the load.
Synchronous Reactance.
The combination of leakage reactance along with armature reaction is called as synchronous reactance.
Ques 73. The maximum power in a synchronous machine is obtained when the load angle is
0 degree
120 degree
90 degree
45 degree
Answer 3. 90 degree
Explanation:
The maximum power can be obtained from a synchronous machine for a power angle δ = 90 degrees. Pm= EV/Xs *sinδ = EV/Xs *sin90o = EV/Xs
For any other power angle power is given as P = Pmsinδ
Ques 74. The 3-phase unbalanced stator current in an alternator or synchronous machine cause
Heating of rotor
Vibration
Double frequency current in the rotor
All of the above
Answer 4. All of the above
Explanation:
The main reason for the unbalanced condition is
When a fault occurs in the stator winding
Open-circuiting of a phase
Failure of circuit breaker contacts
An unbalanced stator fault is not cleared quickly.
The negative sequence component of unbalanced stator current causes double frequency current to be induced in the rotor iron.
If this unbalanced component becomes too high this will cause overheating in the rotor part.
Overheating of the rotor cause eccentricity which produces vibration in the motor.
Ques 75. The method of reducing the harmonic in an alternator is
Well distributed winding
Using short pitch winding
Slots are skewed
All of the above
Answer 4. All of the above
Explanation:
Well distributed winding
Instead of keeping the winding conductor concentrated, it is kept distributed, and due to that there is a considerable reduction in 3rd harmonic at the cost of the slight decrease in induced emf.
Short Pitch winding
Short pitching can be used to eliminate harmonics of a particular order in alternators.
In full pitched coils, as one conductor of a turn in a coil cuts the N(North) pole, the other conductor of the same turn cuts the S(South) pole resulting in the production of induced emf(E).
In short-pitched coils, both conductors of the same turn in a coil don’t cut the respective poles simultaneously.
As a result, the magnitude of induced emf gets reduced to E*Cos(nθ/2), where θ is the chording/short pitching angle ’n’ is an order of harmonic for which the effect of chording is being considered.
Cos(nθ/2) is called the chording factor for the ‘nth’ harmonic.
Skewing
Slots are skewed in order to minimize the effect of voltage resulting from the ripple in the air gap flux produced by the stator slots.
The effect of the number of slots that produce undesirable ripple voltage can be limited by some degree of skew.
Ques 76. In large synchronous generator or alternator, the protection provide for external fault is
Inter-turn fault protection
Sensitive Earth Fault protection
Biased differential protection
All of the above
Answer 4. All of the above
Explanation:
Biased differential protection or Merz-Price Protection
In this method, two sets of an identical current transformer are mounted on either side of the stator phase winding.
The secondaries of the current transformer are connected in star and their ends are connected through pilot wires.
At normal operating conditions, the currents at the two ends of the protected section are the same ( I1 = I2).
When the fault occurs the balance is disturbed and differential current ( I1 = I2) flows through the operating coil of the relay.
This trip the generator circuit breaker to isolate the faulty section.
The relay employed in this protection scheme is generally of electromagnetic type and is arranged for instantaneous operation as the fault is expected to be cleared as quickly as possible.
Sensitive Earth Fault Protection
Sensitive Earth fault protection is normally used on systems where the earth fault current is limited to a very low value.
In sensitive earth fault protection, one dedicated Core Balance CT is used to detect any unbalance in 3 phases and its setting is so low even less than 1 % so it’s called sensitive earth fault protection.
Inter Turn Fault
The coil used in the alternator is the multi-turn coil and the fault that occurs when there is a short that occurs between two turns in a machine winding which are close to each other is called inter-turn Fault.
This fault occurs due to the current surge with a high value of (L × di/dt) voltage across the turns.
Inter turn fault mostly occurs in the stator part of an alternator.
Stator Inter-Turn Fault Protection
Inter-turn faults on the same phase of the stator winding do not disturb the balance between the current in the neutral and high voltage CT’s.
This is the reason why inter-turn fault cannot be detected by longitudinal differential protection.
A biased transverse differential protection is used for protecting the inter-turns fault of the generator.
Ques 77. In an alternator, if the winding is short pitch by 60o electrical its pitch factor will be
0.866
1
0.75
0.28
Answer 1. 0.866
Explanation:
Pitch factor Kp = cos α/2 α =60° Kp = cos 60/2 = cos 30 =0.866
Ques 78. Consider two alternators are running in parallel now if the excitation of the one of the alternators is changed then it will
Reduce speed
Change power factor
Change load demand
Change frequency
Answer 2. Change power factor
Explanation:
Suppose the excitation of the alternator is decreased below normal excitation then reactive power will change and the active power output (W or KW) of the alternator will remain unchanged.
The under-excited alternator delivers a leading current to the infinite bus bar.
It is because the leading current produces an adding m.m.f to increase the under excitation.
Similarly, an overexcited alternator operates at a lagging power factor and supplies lagging reactive power to an infinite bus bar.
Conclusion:
From both of the above conditions i.e whether the excitation is increased or decreased its power factor changes.
Ques 79. The function of the Potier triangle is to separate
Armature voltage and stator voltage
Armature leakage reactance and armature reaction m.m.f.
Potier triangle method is also called as Zero power factor (ZPF) method.
According to this method in any alternator armature resistance drop IRa and the armature leakage reactance drop IXLare basically the e.m.f quantities while armature reaction is considered as m.m.f quantities.
This method is based on the separation of the armature leakage reactance and armature reaction effect.
The armature leakage reactance XL is called a Potier reactance hence this method is also called a Potier reactance method.
Ques 80. Overspeed protection of the generator is done by
The main function of a governor on a generator to sense the speed deviation and adjust the power input( through opening or closing of valves on the steam unit).
The governor will change the power input in proportion to the speed deviation.