Ques.81. A circuit breaker is rated as 1000A, 1000 MVA, 33 kV, 3 sec, 3-phase oil circuit breaker then calculate the value of making current in (kA) of circuit breaker
- 44.61 kA
- 55.32 kA
- 32.32 kA
- 99.99 KA
Ques.82. A 500 kVA, the 3-phase transformer has iron loses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is
- 35%
- 50%
- 70.7%
- 100%
Ques.83. A 3-phase delta/star transformer is supplied at 6000 V on the delta-connected side. The terminal voltage on the secondary side when supplying full load as 0.8 lagging power-factor is 415 V. The equivalent resistance and reactance drops for the transformer are 1% and 5% respectively. The turn’s ratio of the transformer is:
- 14
- 24
- 42
- 20
Ques.84. A 35V source is connected to a series circuit at 600 Ω and RΩ. If a voltmeter of internal resistance is connected across the 600Ω resistor, it reads 5V. The value of R is:
- 1.2 kΩ
- 3.6 kΩ
- 2.4 KΩ
- 7.2 kΩ
Ques.85. At certain current, the energy stored in iron cored coil is 1000 J and its copper loss is 2000 W. The time constant is:
- 1
- 1.5
- 2
- 2.5
Ques.86. Two coils having equal resistance but different inductances are connected in series. The time constant of the series combination is the:
- Sum of the time constant of the individual coils.
- Average of the time constant of the individual coils.
- The geometric mean is of the time constant of individual coils.
- Product of the time constant of the individual coils
Ques.87. The resistance of a strip of copper of rectangular cross section is 2Ω. A metal of resistivity twice that of copper is coated on its upper surface to a thickness equal to that of the copper strip. The resistance of the composite strip will be:
- 2Ω
- 2/3Ω
- 4/3Ω
- 3/4Ω
Ques.88. A 50 kVA, 1000/200 V transformer takes 5 A current at a power factor of 0.2 lagging when connected to 1000 V side at no load is connected at the other side. The core loss in the transformer will be:
- 5000 W
- 3000 W
- 1000 W
- 2000 W
Ques.89. In a transformer, the resistive drop is 2% and reactive drop is 5%. What will be its regulation at full load unity power factor?
- 1%
- 5%
- 2%
- 7%
Ques.90. A pole, 400 V, 60 Hz, 1750 RPM, 3 phase induction motor is connected to 400 V, 50 Hz supply. The motor will:
- Run at speed less than 1750 RPM
- Run at speed more than 1750 RPM
- Burn out
- Not run at all